The PowerLogic PM8310 is the most complete PowerLogic analyser, adding transient and flicker measurement to IEC 61000-4-30 Class A power quality analysis. It is the industry standard for data centre and critical load monitoring.
| Standard PQ | V/I/P/Q/S/PF/Hz · THD · K-factor · unbalance |
| Transients | Short-duration voltage transient detection |
| Flicker | PST + PLT flicker measurement — EN 61000-3-3 |
| Harmonics | Up to the 63rd harmonic — every phase |
| Energy | kWh + kVArh + kVAh — import/export |
| PQ Standard | IEC 61000-4-30 Class A |
| Transients | IEC 61000-4-11 compliant |
| Flicker | EN 61000-3-3 (PST/PLT) |
| Communication | Ethernet Modbus TCP |
| Accuracy | Class 0.2S |
The PM8310 connects to Argus EMS over Modbus TCP over Ethernet, and because a ready register template ships with the platform you do not have to work out a point map on site. The field agent polls the device every 60 seconds by default, writes the reading into a local queue first and then forwards it to the server over MQTT/TLS; nothing is deleted before the server acknowledges it. Hourly and daily summaries are derived from these raw readings, and the consumption and cost screens are fed from the same series.
| Protocol | Modbus TCP over Ethernet |
| Connection path | Directly over Modbus TCP (port 502) — no separate gateway is needed |
| Default polling period | 60 seconds (field agent) |
| Points in the ready template | 44 registers |
| Consumption calculation | Difference of the kWh import index over the period (MAX − MIN) |
| Data assurance | Local queue plus server acknowledgement; nothing is deleted before it is confirmed |
This is a power-quality class device: harmonic components, voltage events and event records are part of the measurement. Questions about reactive penalties, harmonic-driven heating or unexplained failures of sensitive equipment are answered from the records of this class.
The device serves Modbus TCP directly over Ethernet, so no gateway is needed. In exchange, each device needs an IP address on the network and a switch port inside the panel. If more than one master polls the same device at once — a building automation system alongside Argus EMS, for example — its concurrent connection limit has to be respected.