PQ Analyzer Ethernet
Schneider Electric PM8310 PM8000 — Transient + Flicker analizi, data center grade. En kapsamlı PQ analizör.
🔗
Schneider Electric
Official product page (se.com)
● 44 Argus Registers — Ready Template
PM8000

PM8310

The PowerLogic PM8310 is the most complete PowerLogic analyser, adding transient and flicker measurement to IEC 61000-4-30 Class A power quality analysis. It is the industry standard for data centre and critical load monitoring.

Measurement Channels
Standard PQV/I/P/Q/S/PF/Hz · THD · K-factor · unbalance
TransientsShort-duration voltage transient detection
FlickerPST + PLT flicker measurement — EN 61000-3-3
HarmonicsUp to the 63rd harmonic — every phase
EnergykWh + kVArh + kVAh — import/export
Technical Specifications
PQ StandardIEC 61000-4-30 Class A
TransientsIEC 61000-4-11 compliant
FlickerEN 61000-3-3 (PST/PLT)
CommunicationEthernet Modbus TCP
AccuracyClass 0.2S

Integration with Argus EMS

The PM8310 connects to Argus EMS over Modbus TCP over Ethernet, and because a ready register template ships with the platform you do not have to work out a point map on site. The field agent polls the device every 60 seconds by default, writes the reading into a local queue first and then forwards it to the server over MQTT/TLS; nothing is deleted before the server acknowledges it. Hourly and daily summaries are derived from these raw readings, and the consumption and cost screens are fed from the same series.

ProtocolModbus TCP over Ethernet
Connection pathDirectly over Modbus TCP (port 502) — no separate gateway is needed
Default polling period60 seconds (field agent)
Points in the ready template44 registers
Consumption calculationDifference of the kWh import index over the period (MAX − MIN)
Data assuranceLocal queue plus server acknowledgement; nothing is deleted before it is confirmed

When Is This Model the Right Choice?

This is a power-quality class device: harmonic components, voltage events and event records are part of the measurement. Questions about reactive penalties, harmonic-driven heating or unexplained failures of sensitive equipment are answered from the records of this class.

The device serves Modbus TCP directly over Ethernet, so no gateway is needed. In exchange, each device needs an IP address on the network and a switch port inside the panel. If more than one master polls the same device at once — a building automation system alongside Argus EMS, for example — its concurrent connection limit has to be respected.

Frequently Asked Questions

How is the PM8310 connected to Argus EMS?
It connects over Modbus TCP over Ethernet: directly over Modbus TCP (port 502) — no separate gateway is needed. The field agent polls the device every 60 seconds by default, writes the readings into a local queue and forwards them to the server over MQTT/TLS. If the link drops the data waits in the queue and is backfilled once the connection returns.
Does the PM8310 need a register map to be worked out separately?
No. A ready template with 44 points is defined in Argus EMS; you pick the template when adding the device and enter its address and slave ID. The point-by-point mapping step on site disappears, and the same model is read with the same template in every project.
Can the Schneider Electric PM8310 measurement be compared with the electricity invoice?
Yes. The measured kWh index is placed side by side with the invoice from the distribution company, and the distribution charge, YEKDEM and reactive items are shown separately. Bill reconciliation therefore rests on your own meter's index rather than on an estimate.