Heat Meter M-Bus
ZENNER zelsius C5-IUF ZENNER zelsius — Ultrasonik ısı ve soğutma sayacı, DN15–DN40, 105/130 °C. Hareketli parça yok, OMS sertifikalı.
🔗
Schneider Electric
Official product page (se.com)
● 14 Argus Registers — Ready Template
ZENNER zelsius

zelsius C5-IUF

The ZENNER zelsius C5-IUF is a compact heat meter that uses ultrasonic technology to measure heating and cooling energy in buildings. With no moving parts it lasts a long time and needs no inlet or outlet straight run. Open Metering System (OMS) certification gives it direct integration with smart gateways. Connected to Argus EMS over M-Bus TCP, it lets you follow live energy consumption, instant flow and temperature difference.

Measurement Channels
Diameter (DN)DN15, DN20, DN25, DN32, DN40
Nominal Flow (qp)0,6 / 1,5 / 2,5 / 3,5 / 6,0 / 10,0 m³/h
Measurement PrincipleUltrasonic (transit-time)
Max. Temperature105 °C or 130 °C (option-dependent)
Min. Temperature DifferenceΔθ ≥ 3 K
Accuracy ClassClass 2 (EN 1434), MID MI-004
Energy OutputkWh heating + kWh cooling (combined)
Technical Specifications
ProtocolM-Bus EN 13757-2/-3 + Wireless M-Bus / LoRaWAN
ConnectionVia an M-Bus TCP gateway (Argus EMS compatible)
CertificationMID 2014/32/EU MI-004, OMS
Battery≥ 12 years
Protection ClassIP54
MountingHorizontal / vertical — no inlet/outlet straight run required
StandardsEN 1434, MID 2014/32/EU Annex MI-004

Integration with Argus EMS

The zelsius C5-IUF connects to Argus EMS over M-Bus (EN 13757) two-wire meter loop, and because a ready register template ships with the platform you do not have to work out a point map on site. The field agent polls the device every 60 seconds by default, writes the reading into a local queue first and then forwards it to the server over MQTT/TLS; nothing is deleted before the server acknowledges it. Hourly and daily summaries are derived from these raw readings, and the consumption and cost screens are fed from the same series.

ProtocolM-Bus (EN 13757) two-wire meter loop
Connection pathThe M-Bus loop is read through an M-Bus TCP gateway
Default polling period60 seconds (field agent)
Points in the ready template14 registers
Consumption calculationDifference of the heat energy index (kWh) over the period
Data assuranceLocal queue plus server acknowledgement; nothing is deleted before it is confirmed

When Is This Model the Right Choice?

It measures the energy carried in a heating or cooling circuit, evaluating flow together with the supply/return temperature difference. In buildings with central systems this is the measured basis of heat-cost allocation.

The M-Bus loop is two-wire and meters connect in parallel on the same pair, so no dedicated cable is pulled per meter. Loop length, conductor cross-section and the number of meters on the loop are assessed together, because an M-Bus gateway can only drive a limited load. Meter addresses (primary/secondary) are verified one by one during commissioning.

Frequently Asked Questions

How is the zelsius C5-IUF connected to Argus EMS?
It connects over M-Bus (EN 13757) two-wire meter loop: the M-Bus loop is read through an M-Bus TCP gateway. The field agent polls the device every 60 seconds by default, writes the readings into a local queue and forwards them to the server over MQTT/TLS. If the link drops the data waits in the queue and is backfilled once the connection returns.
Does the zelsius C5-IUF need a register map to be worked out separately?
No. A ready template with 14 points is defined in Argus EMS; you pick the template when adding the device and enter its address and slave ID. The point-by-point mapping step on site disappears, and the same model is read with the same template in every project.
Can the zelsius C5-IUF measurement be used for heat cost allocation?
Yes. The period difference of the measured heat energy index is used as the allocation basis per independent unit, and because the reading is remote no manual reading round is needed at the end of the period.