Schneider Electric ION7400 ION7000 — Büyük tesis ve utility grade ölçüm. IEC 61000-4-30, kapsamlı I/O ve veri kaydı.
🔗
Schneider Electric
Official product page (se.com)
● 50 Argus Registers — Ready Template
ION7000

ION7400

The PowerLogic ION7400 is a high-end energy meter designed for large industrial facilities and utility applications. Comprehensive I/O options, advanced power quality analysis and high reliability make it a favourite for critical infrastructure metering.

Measurement Channels
Voltage / CurrentFull phase measurement, high accuracy
HarmonicsUp to the 63rd harmonic — every phase
Power QualityIEC 61000-4-30 Class A — full PQ analysis
EnergyRevenue grade kWh · kVArh · kVAh
EventsSag/swell, interruption and transient logging
Technical Specifications
PQ StandardIEC 61000-4-30 Class A
CommunicationEthernet Modbus TCP · DNP3 · IEC 61850
I/OExtended digital + analogue I/O
Data LoggingComprehensive event log
AccuracyRevenue grade — Class 0.2S

Integration with Argus EMS

The ION7400 connects to Argus EMS over Modbus TCP over Ethernet, and because a ready register template ships with the platform you do not have to work out a point map on site. The field agent polls the device every 60 seconds by default, writes the reading into a local queue first and then forwards it to the server over MQTT/TLS; nothing is deleted before the server acknowledges it. Hourly and daily summaries are derived from these raw readings, and the consumption and cost screens are fed from the same series.

ProtocolModbus TCP over Ethernet
Connection pathDirectly over Modbus TCP (port 502) — no separate gateway is needed
Default polling period60 seconds (field agent)
Points in the ready template50 registers
Consumption calculationDifference of the kWh import index over the period (MAX − MIN)
Data assuranceLocal queue plus server acknowledgement; nothing is deleted before it is confirmed

When Is This Model the Right Choice?

It is made for the most critical points of a facility — transformer outgoers and main busbars — combining high sampling, wide harmonic coverage and event logging. The reference metering point that bill reconciliation relies on is usually chosen from this class.

The device serves Modbus TCP directly over Ethernet, so no gateway is needed. In exchange, each device needs an IP address on the network and a switch port inside the panel. If more than one master polls the same device at once — a building automation system alongside Argus EMS, for example — its concurrent connection limit has to be respected.

Frequently Asked Questions

How is the ION7400 connected to Argus EMS?
It connects over Modbus TCP over Ethernet: directly over Modbus TCP (port 502) — no separate gateway is needed. The field agent polls the device every 60 seconds by default, writes the readings into a local queue and forwards them to the server over MQTT/TLS. If the link drops the data waits in the queue and is backfilled once the connection returns.
Does the ION7400 need a register map to be worked out separately?
No. A ready template with 50 points is defined in Argus EMS; you pick the template when adding the device and enter its address and slave ID. The point-by-point mapping step on site disappears, and the same model is read with the same template in every project.
Can the Schneider Electric ION7400 measurement be compared with the electricity invoice?
Yes. The measured kWh index is placed side by side with the invoice from the distribution company, and the distribution charge, YEKDEM and reactive items are shown separately. Bill reconciliation therefore rests on your own meter's index rather than on an estimate.