Entry+ RS485
Schneider Electric PM2230 PM2000 (EasyLogic) — Alt sayaç ve çok kiracılı binalarda EPDK fatura uyumlu ölçüm. 34 register hazır.
🔗
Schneider Electric
Official product page (se.com)
● 34 Argus Registers — Ready Template
PM2000 (EasyLogic)

PM2230

The EasyLogic PM2230 is an economical power meter optimised for sub-panel incomers in shopping mall common areas and office buildings. It is the most widely used entry-level model for multi-tenant billing and regulatory compliance reporting. 34 register points are pre-defined in Argus.

Measurement Channels
VoltagePhase-neutral + line-line, all phases
CurrentI L1/L2/L3/Neutral — 0.01 A resolution
PowerkW / kVAr / kVA — phase + total
Reactive EnergyQ1 kVArh (inductive) · Q4 kVArh (capacitive)
EnergykWh import · kWh export · kVAh
THDVoltage + Current harmonic distortion
Technical Specifications
AccuracyClass 0.5S (IEC 62053-22)
CommunicationRS485 Modbus RTU · ASCII
Data TypeFLOAT32 Big-Endian + INT64 energy
MountingDIN rail / 96×96 mm panel front
Power Supply100–277 V AC/DC

Integration with Argus EMS

The PM2230 connects to Argus EMS over Modbus RTU over an RS-485 serial line, and because a ready register template ships with the platform you do not have to work out a point map on site. The field agent polls the device every 60 seconds by default, writes the reading into a local queue first and then forwards it to the server over MQTT/TLS; nothing is deleted before the server acknowledges it. Hourly and daily summaries are derived from these raw readings, and the consumption and cost screens are fed from the same series.

ProtocolModbus RTU over an RS-485 serial line
Connection pathThe RS-485 line lands on a Modbus TCP gateway or on the field PC serial port
Default polling period60 seconds (field agent)
Points in the ready template34 registers
Consumption calculationDifference of the kWh import index over the period (MAX − MIN)
Data assuranceLocal queue plus server acknowledgement; nothing is deleted before it is confirmed

When Is This Model the Right Choice?

It puts a wider measurement set on top of the entry level: alongside sub-metering and tenant billing, power factor and demand can be tracked as well. If power quality analysis is needed on the main busbar, a PQ-class device is required.

The device has a serial output, so it joins the existing RS-485 line instead of requiring a dedicated Ethernet run into the panel. The more devices share one line, the longer a polling round takes, which is why the field agent reads each line sequentially and waits 60 ms between devices by default. A slave ID collision and a missing line termination are the two most common commissioning mistakes.

Frequently Asked Questions

How is the PM2230 connected to Argus EMS?
It connects over Modbus RTU over an RS-485 serial line: the RS-485 line lands on a Modbus TCP gateway or on the field PC serial port. The field agent polls the device every 60 seconds by default, writes the readings into a local queue and forwards them to the server over MQTT/TLS. If the link drops the data waits in the queue and is backfilled once the connection returns.
Does the PM2230 need a register map to be worked out separately?
No. A ready template with 34 points is defined in Argus EMS; you pick the template when adding the device and enter its address and slave ID. The point-by-point mapping step on site disappears, and the same model is read with the same template in every project.
Can the Schneider Electric PM2230 measurement be compared with the electricity invoice?
Yes. The measured kWh index is placed side by side with the invoice from the distribution company, and the distribution charge, YEKDEM and reactive items are shown separately. Bill reconciliation therefore rests on your own meter's index rather than on an estimate.