← All Products
Professional RS485
Schneider Electric PM5110 PM5000 — Profesyonel seri, RS485 Modbus, 15. harmonik, 33 alarm, enerji izleme.
🔗
Schneider Electric
Official product page (se.com)
● 43 Argus Registers — Ready Template
PM5000

PM5110

The PowerLogic PM5110 is the standard professional choice for factory panels and energy monitoring projects. Measurement up to the 15th harmonic, 33 configurable alarms and one digital output make integration into industrial automation systems easy.

Measurement Channels
VoltagePhase-neutral + line-line, all phases
CurrentI L1/L2/L3/Neutral — 0.01 A resolution
PowerkW / kVAr / kVA — phase + total
Power FactorPF — phase + total
HarmonicsUp to the 15th harmonic — VTHD + ITHD L1/L2/L3
EnergykWh import/export · Q1 kVArh · Q4 kVArh · kVAh
FrequencyHz — 0.01 Hz resolution
Technical Specifications
AccuracyClass 0.5S (IEC 62053-22)
CommunicationRS485 Modbus RTU
I/O1 digital output (DO)
Alarms33 configurable
Sampling64 sample/cycle
Mounting96×96 mm panel front
Power Supply100–415 V AC · 125–250 V DC

Integration with Argus EMS

The PM5110 connects to Argus EMS over Modbus RTU over an RS-485 serial line, and because a ready register template ships with the platform you do not have to work out a point map on site. The field agent polls the device every 60 seconds by default, writes the reading into a local queue first and then forwards it to the server over MQTT/TLS; nothing is deleted before the server acknowledges it. Hourly and daily summaries are derived from these raw readings, and the consumption and cost screens are fed from the same series.

ProtocolModbus RTU over an RS-485 serial line
Connection pathThe RS-485 line lands on a Modbus TCP gateway or on the field PC serial port
Default polling period60 seconds (field agent)
Points in the ready template43 registers
Consumption calculationDifference of the kWh import index over the period (MAX − MIN)
Data assuranceLocal queue plus server acknowledgement; nothing is deleted before it is confirmed

When Is This Model the Right Choice?

It is built for main distribution boards and critical loads: alongside energy and demand, the basic power quality quantities are reported too. Reactive penalty tracking and compensation assessment become reliable from this level upwards.

The device has a serial output, so it joins the existing RS-485 line instead of requiring a dedicated Ethernet run into the panel. The more devices share one line, the longer a polling round takes, which is why the field agent reads each line sequentially and waits 60 ms between devices by default. A slave ID collision and a missing line termination are the two most common commissioning mistakes.

Frequently Asked Questions

How is the PM5110 connected to Argus EMS?
It connects over Modbus RTU over an RS-485 serial line: the RS-485 line lands on a Modbus TCP gateway or on the field PC serial port. The field agent polls the device every 60 seconds by default, writes the readings into a local queue and forwards them to the server over MQTT/TLS. If the link drops the data waits in the queue and is backfilled once the connection returns.
Does the PM5110 need a register map to be worked out separately?
No. A ready template with 43 points is defined in Argus EMS; you pick the template when adding the device and enter its address and slave ID. The point-by-point mapping step on site disappears, and the same model is read with the same template in every project.
Can the Schneider Electric PM5110 measurement be compared with the electricity invoice?
Yes. The measured kWh index is placed side by side with the invoice from the distribution company, and the distribution charge, YEKDEM and reactive items are shown separately. Bill reconciliation therefore rests on your own meter's index rather than on an estimate.